1* Thermal Framework Device Tree descriptor
2
3This file describes a generic binding to provide a way of
4defining hardware thermal structure using device tree.
5A thermal structure includes thermal zones and their components,
6such as trip points, polling intervals, sensors and cooling devices
7binding descriptors.
8
9The target of device tree thermal descriptors is to describe only
10the hardware thermal aspects. The thermal device tree bindings are
11not about how the system must control or which algorithm or policy
12must be taken in place.
13
14There are five types of nodes involved to describe thermal bindings:
15- thermal sensors: devices which may be used to take temperature
16  measurements.
17- cooling devices: devices which may be used to dissipate heat.
18- trip points: describe key temperatures at which cooling is recommended. The
19  set of points should be chosen based on hardware limits.
20- cooling maps: used to describe links between trip points and cooling devices;
21- thermal zones: used to describe thermal data within the hardware;
22
23The following is a description of each of these node types.
24
25* Thermal sensor devices
26
27Thermal sensor devices are nodes providing temperature sensing capabilities on
28thermal zones. Typical devices are I2C ADC converters and bandgaps. These are
29nodes providing temperature data to thermal zones. Thermal sensor devices may
30control one or more internal sensors.
31
32Required property:
33- #thermal-sensor-cells: Used to provide sensor device specific information
34  Type: unsigned	 while referring to it. Typically 0 on thermal sensor
35  Size: one cell	 nodes with only one sensor, and at least 1 on nodes
36			 with several internal sensors, in order
37			 to identify uniquely the sensor instances within
38			 the IC. See thermal zone binding for more details
39			 on how consumers refer to sensor devices.
40
41* Cooling device nodes
42
43Cooling devices are nodes providing control on power dissipation. There
44are essentially two ways to provide control on power dissipation. First
45is by means of regulating device performance, which is known as passive
46cooling. A typical passive cooling is a CPU that has dynamic voltage and
47frequency scaling (DVFS), and uses lower frequencies as cooling states.
48Second is by means of activating devices in order to remove
49the dissipated heat, which is known as active cooling, e.g. regulating
50fan speeds. In both cases, cooling devices shall have a way to determine
51the state of cooling in which the device is.
52
53Any cooling device has a range of cooling states (i.e. different levels
54of heat dissipation). For example a fan's cooling states correspond to
55the different fan speeds possible. Cooling states are referred to by
56single unsigned integers, where larger numbers mean greater heat
57dissipation. The precise set of cooling states associated with a device
58(as referred to be the cooling-min-state and cooling-max-state
59properties) should be defined in a particular device's binding.
60For more examples of cooling devices, refer to the example sections below.
61
62Required properties:
63- cooling-min-state:	An integer indicating the smallest
64  Type: unsigned	cooling state accepted. Typically 0.
65  Size: one cell
66
67- cooling-max-state:	An integer indicating the largest
68  Type: unsigned	cooling state accepted.
69  Size: one cell
70
71- #cooling-cells:	Used to provide cooling device specific information
72  Type: unsigned	while referring to it. Must be at least 2, in order
73  Size: one cell      	to specify minimum and maximum cooling state used
74			in the reference. The first cell is the minimum
75			cooling state requested and the second cell is
76			the maximum cooling state requested in the reference.
77			See Cooling device maps section below for more details
78			on how consumers refer to cooling devices.
79
80* Trip points
81
82The trip node is a node to describe a point in the temperature domain
83in which the system takes an action. This node describes just the point,
84not the action.
85
86Required properties:
87- temperature:		An integer indicating the trip temperature level,
88  Type: signed		in millicelsius.
89  Size: one cell
90
91- hysteresis:		A low hysteresis value on temperature property (above).
92  Type: unsigned	This is a relative value, in millicelsius.
93  Size: one cell
94
95- type:			a string containing the trip type. Expected values are:
96	"active":	A trip point to enable active cooling
97	"passive":	A trip point to enable passive cooling
98	"hot":		A trip point to notify emergency
99	"critical":	Hardware not reliable.
100  Type: string
101
102* Cooling device maps
103
104The cooling device maps node is a node to describe how cooling devices
105get assigned to trip points of the zone. The cooling devices are expected
106to be loaded in the target system.
107
108Required properties:
109- cooling-device:	A phandle of a cooling device with its specifier,
110  Type: phandle +	referring to which cooling device is used in this
111    cooling specifier	binding. In the cooling specifier, the first cell
112			is the minimum cooling state and the second cell
113			is the maximum cooling state used in this map.
114- trip:			A phandle of a trip point node within the same thermal
115  Type: phandle of	zone.
116   trip point node
117
118Optional property:
119- contribution:		The cooling contribution to the thermal zone of the
120  Type: unsigned	referred cooling device at the referred trip point.
121  Size: one cell      	The contribution is a ratio of the sum
122			of all cooling contributions within a thermal zone.
123
124Note: Using the THERMAL_NO_LIMIT (-1UL) constant in the cooling-device phandle
125limit specifier means:
126(i)   - minimum state allowed for minimum cooling state used in the reference.
127(ii)  - maximum state allowed for maximum cooling state used in the reference.
128Refer to include/dt-bindings/thermal/thermal.h for definition of this constant.
129
130* Thermal zone nodes
131
132The thermal zone node is the node containing all the required info
133for describing a thermal zone, including its cooling device bindings. The
134thermal zone node must contain, apart from its own properties, one sub-node
135containing trip nodes and one sub-node containing all the zone cooling maps.
136
137Required properties:
138- polling-delay:	The maximum number of milliseconds to wait between polls
139  Type: unsigned	when checking this thermal zone.
140  Size: one cell
141
142- polling-delay-passive: The maximum number of milliseconds to wait
143  Type: unsigned	between polls when performing passive cooling.
144  Size: one cell
145
146- thermal-sensors:	A list of thermal sensor phandles and sensor specifier
147  Type: list of 	used while monitoring the thermal zone.
148  phandles + sensor
149  specifier
150
151- trips:		A sub-node which is a container of only trip point nodes
152  Type: sub-node	required to describe the thermal zone.
153
154- cooling-maps:		A sub-node which is a container of only cooling device
155  Type: sub-node	map nodes, used to describe the relation between trips
156			and cooling devices.
157
158Optional property:
159- coefficients:		An array of integers (one signed cell) containing
160  Type: array		coefficients to compose a linear relation between
161  Elem size: one cell	the sensors listed in the thermal-sensors property.
162  Elem type: signed	Coefficients defaults to 1, in case this property
163			is not specified. A simple linear polynomial is used:
164			Z = c0 * x0 + c1 + x1 + ... + c(n-1) * x(n-1) + cn.
165
166			The coefficients are ordered and they match with sensors
167			by means of sensor ID. Additional coefficients are
168			interpreted as constant offset.
169
170Note: The delay properties are bound to the maximum dT/dt (temperature
171derivative over time) in two situations for a thermal zone:
172(i)  - when passive cooling is activated (polling-delay-passive); and
173(ii) - when the zone just needs to be monitored (polling-delay) or
174when active cooling is activated.
175
176The maximum dT/dt is highly bound to hardware power consumption and dissipation
177capability. The delays should be chosen to account for said max dT/dt,
178such that a device does not cross several trip boundaries unexpectedly
179between polls. Choosing the right polling delays shall avoid having the
180device in temperature ranges that may damage the silicon structures and
181reduce silicon lifetime.
182
183* The thermal-zones node
184
185The "thermal-zones" node is a container for all thermal zone nodes. It shall
186contain only sub-nodes describing thermal zones as in the section
187"Thermal zone nodes". The "thermal-zones" node appears under "/".
188
189* Examples
190
191Below are several examples on how to use thermal data descriptors
192using device tree bindings:
193
194(a) - CPU thermal zone
195
196The CPU thermal zone example below describes how to setup one thermal zone
197using one single sensor as temperature source and many cooling devices and
198power dissipation control sources.
199
200#include <dt-bindings/thermal/thermal.h>
201
202cpus {
203	/*
204	 * Here is an example of describing a cooling device for a DVFS
205	 * capable CPU. The CPU node describes its four OPPs.
206	 * The cooling states possible are 0..3, and they are
207	 * used as OPP indexes. The minimum cooling state is 0, which means
208	 * all four OPPs can be available to the system. The maximum
209	 * cooling state is 3, which means only the lowest OPPs (198MHz@0.85V)
210	 * can be available in the system.
211	 */
212	cpu0: cpu@0 {
213		...
214		operating-points = <
215			/* kHz    uV */
216			970000  1200000
217			792000  1100000
218			396000  950000
219			198000  850000
220		>;
221		cooling-min-state = <0>;
222		cooling-max-state = <3>;
223		#cooling-cells = <2>; /* min followed by max */
224	};
225	...
226};
227
228&i2c1 {
229	...
230	/*
231	 * A simple fan controller which supports 10 speeds of operation
232	 * (represented as 0-9).
233	 */
234	fan0: fan@0x48 {
235		...
236		cooling-min-state = <0>;
237		cooling-max-state = <9>;
238		#cooling-cells = <2>; /* min followed by max */
239	};
240};
241
242ocp {
243	...
244	/*
245	 * A simple IC with a single bandgap temperature sensor.
246	 */
247	bandgap0: bandgap@0x0000ED00 {
248		...
249		#thermal-sensor-cells = <0>;
250	};
251};
252
253thermal-zones {
254	cpu_thermal: cpu-thermal {
255		polling-delay-passive = <250>; /* milliseconds */
256		polling-delay = <1000>; /* milliseconds */
257
258		thermal-sensors = <&bandgap0>;
259
260		trips {
261			cpu_alert0: cpu-alert0 {
262				temperature = <90000>; /* millicelsius */
263				hysteresis = <2000>; /* millicelsius */
264				type = "active";
265			};
266			cpu_alert1: cpu-alert1 {
267				temperature = <100000>; /* millicelsius */
268				hysteresis = <2000>; /* millicelsius */
269				type = "passive";
270			};
271			cpu_crit: cpu-crit {
272				temperature = <125000>; /* millicelsius */
273				hysteresis = <2000>; /* millicelsius */
274				type = "critical";
275			};
276		};
277
278		cooling-maps {
279			map0 {
280				trip = <&cpu_alert0>;
281				cooling-device = <&fan0 THERMAL_NO_LIMIT 4>;
282			};
283			map1 {
284				trip = <&cpu_alert1>;
285				cooling-device = <&fan0 5 THERMAL_NO_LIMIT>;
286			};
287			map2 {
288				trip = <&cpu_alert1>;
289				cooling-device =
290				    <&cpu0 THERMAL_NO_LIMIT THERMAL_NO_LIMIT>;
291			};
292		};
293	};
294};
295
296In the example above, the ADC sensor (bandgap0) at address 0x0000ED00 is
297used to monitor the zone 'cpu-thermal' using its sole sensor. A fan
298device (fan0) is controlled via I2C bus 1, at address 0x48, and has ten
299different cooling states 0-9. It is used to remove the heat out of
300the thermal zone 'cpu-thermal' using its cooling states
301from its minimum to 4, when it reaches trip point 'cpu_alert0'
302at 90C, as an example of active cooling. The same cooling device is used at
303'cpu_alert1', but from 5 to its maximum state. The cpu@0 device is also
304linked to the same thermal zone, 'cpu-thermal', as a passive cooling device,
305using all its cooling states at trip point 'cpu_alert1',
306which is a trip point at 100C. On the thermal zone 'cpu-thermal', at the
307temperature of 125C, represented by the trip point 'cpu_crit', the silicon
308is not reliable anymore.
309
310(b) - IC with several internal sensors
311
312The example below describes how to deploy several thermal zones based off a
313single sensor IC, assuming it has several internal sensors. This is a common
314case on SoC designs with several internal IPs that may need different thermal
315requirements, and thus may have their own sensor to monitor or detect internal
316hotspots in their silicon.
317
318#include <dt-bindings/thermal/thermal.h>
319
320ocp {
321	...
322	/*
323	 * A simple IC with several bandgap temperature sensors.
324	 */
325	bandgap0: bandgap@0x0000ED00 {
326		...
327		#thermal-sensor-cells = <1>;
328	};
329};
330
331thermal-zones {
332	cpu_thermal: cpu-thermal {
333		polling-delay-passive = <250>; /* milliseconds */
334		polling-delay = <1000>; /* milliseconds */
335
336				/* sensor       ID */
337		thermal-sensors = <&bandgap0     0>;
338
339		trips {
340			/* each zone within the SoC may have its own trips */
341			cpu_alert: cpu-alert {
342				temperature = <100000>; /* millicelsius */
343				hysteresis = <2000>; /* millicelsius */
344				type = "passive";
345			};
346			cpu_crit: cpu-crit {
347				temperature = <125000>; /* millicelsius */
348				hysteresis = <2000>; /* millicelsius */
349				type = "critical";
350			};
351		};
352
353		cooling-maps {
354			/* each zone within the SoC may have its own cooling */
355			...
356		};
357	};
358
359	gpu_thermal: gpu-thermal {
360		polling-delay-passive = <120>; /* milliseconds */
361		polling-delay = <1000>; /* milliseconds */
362
363				/* sensor       ID */
364		thermal-sensors = <&bandgap0     1>;
365
366		trips {
367			/* each zone within the SoC may have its own trips */
368			gpu_alert: gpu-alert {
369				temperature = <90000>; /* millicelsius */
370				hysteresis = <2000>; /* millicelsius */
371				type = "passive";
372			};
373			gpu_crit: gpu-crit {
374				temperature = <105000>; /* millicelsius */
375				hysteresis = <2000>; /* millicelsius */
376				type = "critical";
377			};
378		};
379
380		cooling-maps {
381			/* each zone within the SoC may have its own cooling */
382			...
383		};
384	};
385
386	dsp_thermal: dsp-thermal {
387		polling-delay-passive = <50>; /* milliseconds */
388		polling-delay = <1000>; /* milliseconds */
389
390				/* sensor       ID */
391		thermal-sensors = <&bandgap0     2>;
392
393		trips {
394			/* each zone within the SoC may have its own trips */
395			dsp_alert: dsp-alert {
396				temperature = <90000>; /* millicelsius */
397				hysteresis = <2000>; /* millicelsius */
398				type = "passive";
399			};
400			dsp_crit: gpu-crit {
401				temperature = <135000>; /* millicelsius */
402				hysteresis = <2000>; /* millicelsius */
403				type = "critical";
404			};
405		};
406
407		cooling-maps {
408			/* each zone within the SoC may have its own cooling */
409			...
410		};
411	};
412};
413
414In the example above, there is one bandgap IC which has the capability to
415monitor three sensors. The hardware has been designed so that sensors are
416placed on different places in the DIE to monitor different temperature
417hotspots: one for CPU thermal zone, one for GPU thermal zone and the
418other to monitor a DSP thermal zone.
419
420Thus, there is a need to assign each sensor provided by the bandgap IC
421to different thermal zones. This is achieved by means of using the
422#thermal-sensor-cells property and using the first cell of the sensor
423specifier as sensor ID. In the example, then, <bandgap 0> is used to
424monitor CPU thermal zone, <bandgap 1> is used to monitor GPU thermal
425zone and <bandgap 2> is used to monitor DSP thermal zone. Each zone
426may be uncorrelated, having its own dT/dt requirements, trips
427and cooling maps.
428
429
430(c) - Several sensors within one single thermal zone
431
432The example below illustrates how to use more than one sensor within
433one thermal zone.
434
435#include <dt-bindings/thermal/thermal.h>
436
437&i2c1 {
438	...
439	/*
440	 * A simple IC with a single temperature sensor.
441	 */
442	adc: sensor@0x49 {
443		...
444		#thermal-sensor-cells = <0>;
445	};
446};
447
448ocp {
449	...
450	/*
451	 * A simple IC with a single bandgap temperature sensor.
452	 */
453	bandgap0: bandgap@0x0000ED00 {
454		...
455		#thermal-sensor-cells = <0>;
456	};
457};
458
459thermal-zones {
460	cpu_thermal: cpu-thermal {
461		polling-delay-passive = <250>; /* milliseconds */
462		polling-delay = <1000>; /* milliseconds */
463
464		thermal-sensors = <&bandgap0>,	/* cpu */
465				  <&adc>;	/* pcb north */
466
467		/* hotspot = 100 * bandgap - 120 * adc + 484 */
468		coefficients = 		<100	-120	484>;
469
470		trips {
471			...
472		};
473
474		cooling-maps {
475			...
476		};
477	};
478};
479
480In some cases, there is a need to use more than one sensor to extrapolate
481a thermal hotspot in the silicon. The above example illustrates this situation.
482For instance, it may be the case that a sensor external to CPU IP may be placed
483close to CPU hotspot and together with internal CPU sensor, it is used
484to determine the hotspot. Assuming this is the case for the above example,
485the hypothetical extrapolation rule would be:
486		hotspot = 100 * bandgap - 120 * adc + 484
487
488In other context, the same idea can be used to add fixed offset. For instance,
489consider the hotspot extrapolation rule below:
490		hotspot = 1 * adc + 6000
491
492In the above equation, the hotspot is always 6C higher than what is read
493from the ADC sensor. The binding would be then:
494        thermal-sensors =  <&adc>;
495
496		/* hotspot = 1 * adc + 6000 */
497	coefficients = 		<1	6000>;
498
499(d) - Board thermal
500
501The board thermal example below illustrates how to setup one thermal zone
502with many sensors and many cooling devices.
503
504#include <dt-bindings/thermal/thermal.h>
505
506&i2c1 {
507	...
508	/*
509	 * An IC with several temperature sensor.
510	 */
511	adc_dummy: sensor@0x50 {
512		...
513		#thermal-sensor-cells = <1>; /* sensor internal ID */
514	};
515};
516
517thermal-zones {
518	batt-thermal {
519		polling-delay-passive = <500>; /* milliseconds */
520		polling-delay = <2500>; /* milliseconds */
521
522				/* sensor       ID */
523		thermal-sensors = <&adc_dummy     4>;
524
525		trips {
526			...
527		};
528
529		cooling-maps {
530			...
531		};
532	};
533
534	board_thermal: board-thermal {
535		polling-delay-passive = <1000>; /* milliseconds */
536		polling-delay = <2500>; /* milliseconds */
537
538				/* sensor       ID */
539		thermal-sensors = <&adc_dummy     0>, /* pcb top edge */
540				  <&adc_dummy     1>, /* lcd */
541				  <&adc_dummy     2>; /* back cover */
542		/*
543		 * An array of coefficients describing the sensor
544		 * linear relation. E.g.:
545		 * z = c1*x1 + c2*x2 + c3*x3
546		 */
547		coefficients =		<1200	-345	890>;
548
549		trips {
550			/* Trips are based on resulting linear equation */
551			cpu_trip: cpu-trip {
552				temperature = <60000>; /* millicelsius */
553				hysteresis = <2000>; /* millicelsius */
554				type = "passive";
555			};
556			gpu_trip: gpu-trip {
557				temperature = <55000>; /* millicelsius */
558				hysteresis = <2000>; /* millicelsius */
559				type = "passive";
560			}
561			lcd_trip: lcp-trip {
562				temperature = <53000>; /* millicelsius */
563				hysteresis = <2000>; /* millicelsius */
564				type = "passive";
565			};
566			crit_trip: crit-trip {
567				temperature = <68000>; /* millicelsius */
568				hysteresis = <2000>; /* millicelsius */
569				type = "critical";
570			};
571		};
572
573		cooling-maps {
574			map0 {
575				trip = <&cpu_trip>;
576				cooling-device = <&cpu0 0 2>;
577				contribution = <55>;
578			};
579			map1 {
580				trip = <&gpu_trip>;
581				cooling-device = <&gpu0 0 2>;
582				contribution = <20>;
583			};
584			map2 {
585				trip = <&lcd_trip>;
586				cooling-device = <&lcd0 5 10>;
587				contribution = <15>;
588			};
589		};
590	};
591};
592
593The above example is a mix of previous examples, a sensor IP with several internal
594sensors used to monitor different zones, one of them is composed by several sensors and
595with different cooling devices.
596